A 115-kV transmission line has a positive sequence impedance of 28280 ohms (primary). a. You...

90.2K

Verified Solution

Question

Accounting

image

A 115-kV transmission line has a positive sequence impedance of 28280 ohms (primary). a. You are to set a Zone 1 mho-type phase distance (21-1) relay to cover 85% of the line and a Zone 2 (21-2) relay to cover 125% of the line. For better resistive fault coverage, the relay maximum reach angles are set to 60. Determine the required relay reach settings (at the relay reach angle). Instrument transformer ratios are given as: CTR = 1200/5A and VTR = 1000/1V. b. Assuming a lagging power factor limit of 0.87, how much load (in primary MVA) can the Zone 2 relay carry at 1.Opu voltage? Don't worry about any additional safety margins or reduced voltage conditions

Answer & Explanation Solved by verified expert
Get Answers to Unlimited Questions

Join us to gain access to millions of questions and expert answers. Enjoy exclusive benefits tailored just for you!

Membership Benefits:
  • Unlimited Question Access with detailed Answers
  • Zin AI - 3 Million Words
  • 10 Dall-E 3 Images
  • 20 Plot Generations
  • Conversation with Dialogue Memory
  • No Ads, Ever!
  • Access to Our Best AI Platform: Flex AI - Your personal assistant for all your inquiries!
Become a Member

Other questions asked by students