7-7 Consider the same compressor as problems 7-5 and 7-6.Calculate the rate of entropy generation (in kW/K) of the realcompressor.
Solutions:
Problem 7-1 & 7-2
7-1 Your company wants to buy a compressor that will operateadiabatically to compress 2 kg/s of saturated R-134a vapor at -15°Cto a pressure of 1000 kPa. What is the minimum work (in kW)required? Use the right sign convention for work. Hint: The minimumwork is that of the reversible process. Start by simplifying theentropy balance!
Ans: W = -75.92
7-2 Consider the same situation as problem 7-1. Your companywants to buy a compressor that will operate adiabatically tocompress 2 kg/s of saturated R-134a vapor at -15°C to a pressure of1000 kPa. What is the minimum outlet temperature (in°C) required?Hint: just like before, the minimum outlet temperature occurs whenthe process is reversible.
Ans: T2 = 47
7-5 You build the compressor from Participation Problems 7-1 and7-2 and find that the exit temperature is actually 60°C. If thereal compressor is still adiabatic, what is the real work (in kW) ?Use the right sign convention for work.
Ans: -105.38
7-6 Consider the same compressor from Participation Problems 7-5with a real exit temperature of 60°C. What is the efficiency(expressed as a %) of the compressor?
Ans: 71.4